Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02720
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLAN CALL FOR #2 BARE GROUND ELECTRODE CONDUCTOR BONDED TO MODULAR STEEL 2) EXPOSE GROUND ROD CONNECTIONS 3) NO EQUIPMENT GROUND RUN WITH FEEDERS VERIFY CONDITIONS AS REQUIRED IN 250.32.2 HAVE BEEN MET 4) I.D. CIRCUIT BREAKERS IN MODULAR PANEL 5) INSTALL HOLDOWN DEVICE ON MAIN BACK FED BREAKER AS REQUIRED 408.36 F NEC 6) REVISE PLAN TO SHOW ACTUAL INSTALLATION |
|
10/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BATHROOM WALLS |