Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH |
|
| 08/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT VDV CABLING ABOVE CEILING TO 725.24, 800.24, 300.11 2. EXISTING RECEPTACLES TO BE AS PER 517.13 3. SWITCHES TO BE AS PER 517.13 |