Permit: T08CM02690

Parcel: 132130480


Addresses:

1001 E BENSON HY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/11/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/10/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MC CABLE NOT TO BE BUNDLED IN LENGTHS
OVER 24" 310.15 B2 NEC WITHOUT DERATING
2. MC TO BE SUPPORTED PER 330.30 NEC
12/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*