Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/31/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN EQUIPMENT NOT CONTAINED WITHIN HOOD CANOPY 2) INTERLOCK FOR HOOD EXHAUST ACTIVIATION NOT WORKING 3) ALL PVC PIPING MUST USE PRIMER PRIOR TO GLUE 4) ALL PVC EXPOSED TO EXTERIOR MUST BE PAINTED TO PROTECT IT FROM U.V. 5) PROVIDE PROPER WIRE SIZE AT RECOVERY UNIT TRU-2 6) DUCT SMOKE DETECTORS NOT WORKING PROPERLY 7) AIR BALANCE REPORT OK |