Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM02688
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/05/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/31/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN EQUIPMENT NOT CONTAINED WITHIN HOOD CANOPY 2) INTERLOCK FOR HOOD EXHAUST ACTIVIATION NOT WORKING 3) ALL PVC PIPING MUST USE PRIMER PRIOR TO GLUE 4) ALL PVC EXPOSED TO EXTERIOR MUST BE PAINTED TO PROTECT IT FROM U.V. 5) PROVIDE PROPER WIRE SIZE AT RECOVERY UNIT TRU-2 6) DUCT SMOKE DETECTORS NOT WORKING PROPERLY 7) AIR BALANCE REPORT OK |