Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02688

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/31/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INTERIOR SIGNS TO BE LISTED 600.3
2) BATHROOM EM LIGHTING TO BE PER 700.12(F)
3) WAITING OF LETTER FOR M/C CABLE
4) OK TO TILE
12/29/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
No work progress from previous inspection
Pleas pay refee before next inspection
12/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO WORK PROGRESS
A REFEE MAY BE ASSESSED
12/23/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
OPEN TILES TO INSPECT -- NO CLEARANCE WAS GIVEN
FINISH PREVIOUS ITEMS
12/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CLEAN EXCESS FOREIGN MATERIAL FROM BOTTOM OF PANELS
2) FINISH ITEMS 2 & 7 PREVIOUS INSPECTION
12/18/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*A BOND WILL BE NEEDED TO BE POSTED FOR TEMP POWER
1. FINISH SUPPORT WIRES FOR FIXTURES & EXIT LIGHTS
2. VDV CABLING NOT TO BE SUPPORTED BY CONDUIT
3. PLEASE VERIFY BOX FILL (D-2/2,4,6)
4. BOND ENCLOSURE FOR HOOD OTHER THAN DOOR
5. BOND CONTACTOR ENCLOSURE
6. TIGHTEN LOOSE FITTING ABOVE PANEL
7. SEAL UNUSED CONDUIT OPENINGS ABOVE PANEL
8. SEAL RACEWAY TO WALK IN BOX PER 300.7
11/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & HARD LIDS

PLEASE VERIFY IF MC IS OK
11/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DEMISING WALL