Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM02686
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2008 | PLUMBING - FINAL | Approved | CORRECTIONS OK. WASHER IS NSF LISTED PER ANSI 1004. | |
12/03/2008 | PLUMBING - FINAL | Not ready for Inspection | 1. ALL RP DEVICES TO BE SUPPLIED WITH MINIMUM 1/2" COPPER 2. ALL I.W DRAINS TO BE APPROVED MATERIAL 3. CONNECT CABLE RESTRAINTS ON PORTABLE GAS APPLIANCES - WHERE IS ANSUL? 4. SEE NOTES FROM 11/26/08 - YOUR PAPERWORK IS NOT A LISTING AS REQUESTED AND DOES NOT STATE - TESTED UNDER ACTUAL BACKFLOW CONDITIONS 5. THERE ARE A NUMBER OF QUESTIONS I NEED TO ASK THE PLUMBER -- PLEASE HAVE HIM ON SITE AT THE NEXT INSPECTION. 6. CONTINUED "NOT READY" WILL RESULT IN REINSPECTION FEE |
|
11/26/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) DW U34 BUILT IN AG DOES NOT APPEAR TO COMPLY WITH UPC SIDE WALL CLEARANCES. PROVIDE THIRD PARTY LISTING OR INSTALL RPA 2) ALL OTHER BACKFLOW CERTS RECEIVED. BACTERIA REPORT RECEIVED |
|
11/21/2008 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE BAC-T REPORT FOR POTABLE WATER 2. PROVIDE BACKFLOW CERTIFICATIONS FOR ALL DEVICES IN KITCHEN |
|
11/20/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL WORK BEFORE CALLING FOR INSPECTIONS |