Permit: T08CM02685

Parcel: 10321029W

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. TIGHTEN LOOSE FITTINGS AND SUPPORT SEALTITE
2. GROUND DISCONNECT ENCLOSURE
3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS IN RACEWAYS TO BE COLOR ENTIRE LENGTH
4. LABEL DISCONNECTING MEANS

STORE:
1. SUPPORT M/C CABLE ABOVE CEILING
AS PER 330.17, 330.30, 300.11
2. SUPPORT UNCABLING AS PER 725.3 & 24, 800.3 & 24, 300.11
3. CLEAN EXCESS TRASH FROM CEILING TILES
4. FIXTURES/CANS TO BE SUPPORTED PER 410.16 ALSO, SUPPORT WIRES ARE NEEDED
5. FILL UNUSED OPENINGS IN BOXES
6. SUPPORT M/C CABLES ABOVE SWITCHGEAR AND PROPERLY INSTALL FITTINGS
7. CONDUCTORS TO ENTER SWITCHBOARD IN SECTION SERVED - 408.3
8. LETTER FROM ARCVISION DOES NOT ADDRESS PANEL SCHEDULE CHANGES OR LOAD CALCULATIONS -- NO BUILDING DEPARTMENT APPROVED IS ON SITE ALSO, DELETION OF OUTLETS
9. FINISH PREVIOUS ITEMS FROM 11/19/08 ALSO 314.21
10. DISCONNECT NEEDED AT ICE MACHINE 440

A REFEE MAY BE ASSESSED PER ADMIN. CODE
12/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
11/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ELECTRIC IN USE WITHOUT APPROVAL
2. WORK NOT AS PER PLANS - REVISE PLANS TO REFLECT WORK DONE
3. BOXES NOT FLUSH IN COMBUSTIBLES OR MORE THAN 1/4" IN NON-COMBUSTIBLES -- 314.20