Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOF: 1. TIGHTEN LOOSE FITTINGS AND SUPPORT SEALTITE 2. GROUND DISCONNECT ENCLOSURE 3. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS IN RACEWAYS TO BE COLOR ENTIRE LENGTH 4. LABEL DISCONNECTING MEANS STORE: 1. SUPPORT M/C CABLE ABOVE CEILING AS PER 330.17, 330.30, 300.11 2. SUPPORT UNCABLING AS PER 725.3 & 24, 800.3 & 24, 300.11 3. CLEAN EXCESS TRASH FROM CEILING TILES 4. FIXTURES/CANS TO BE SUPPORTED PER 410.16 ALSO, SUPPORT WIRES ARE NEEDED 5. FILL UNUSED OPENINGS IN BOXES 6. SUPPORT M/C CABLES ABOVE SWITCHGEAR AND PROPERLY INSTALL FITTINGS 7. CONDUCTORS TO ENTER SWITCHBOARD IN SECTION SERVED - 408.3 8. LETTER FROM ARCVISION DOES NOT ADDRESS PANEL SCHEDULE CHANGES OR LOAD CALCULATIONS -- NO BUILDING DEPARTMENT APPROVED IS ON SITE ALSO, DELETION OF OUTLETS 9. FINISH PREVIOUS ITEMS FROM 11/19/08 ALSO 314.21 10. DISCONNECT NEEDED AT ICE MACHINE 440 A REFEE MAY BE ASSESSED PER ADMIN. CODE |
|
| 12/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 11/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ELECTRIC IN USE WITHOUT APPROVAL 2. WORK NOT AS PER PLANS - REVISE PLANS TO REFLECT WORK DONE 3. BOXES NOT FLUSH IN COMBUSTIBLES OR MORE THAN 1/4" IN NON-COMBUSTIBLES -- 314.20 |