Permit: T08CM02682

Parcel: 13348128C


Addresses:

30 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02682

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINAL PENDING APPROVAL OF RED LINE DRAWINGS SUBMITTED TO CITY PLAN REVIEW
06/30/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL INSPECTION ITEMS FROM 11/19/08
2) NEED TO PROVIDE RED LINE DRAWINGS FOR ALL CHANGES IN FIELD
3) HAVE COMPLETE BY NEXT INSPECTION OR WILL HAVE TO PAY RE-INSPECTION FEE
06/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Electrical contractor to be on site for all further inspections
Need to provide ladder for above ceiling inspection
Plans left on site have no electric sheet
Ensure all items from inspection on 11/19/08 have been completed
Pay reinspection fee prior to next inspection
03/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NEED TO HAVE APPROVED PLANS ON SITE.
HAVE ELECTRICAL CONTRACTOR GO THROUGH ENTIRE JOB INSTALL PER APPROVED PLANS AND NEC.
NEXT INSPECTION WILL RESULT IN REFEE IF ABOVE ITEMS NOT COMPLETE
11/19/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALLATION NOT PER PLANS. INSTALL PER PLANS OR REVISE PLANS
2. STRAP MC CABLE WITHIN 12" OF CONNECTIONS
AND EVERY 6' BETWEEN. NOT TO LAY ON CEILING
3. REMOVE OLD WIRING
4. GROUND METAL BOXES
5. SEAL OPEN KNOCKOUTS
6. JUNCTION BOXES OVERFILLED. NEED 6" OF FREE CONDUCTOR LENGTH
7. USE CONNECTORS ON MC WHERE ENTER EQUIPMENT OR RACEWAYS
8. RE-IDENTIFY WHITE WIRES USED AS PHASE CONDUCTORS
9. NEED UPDATED PANEL SCHEDULES
10. WHERE ARE ALL NEW CIRCUITS SHOWN ON PLANS
11. SEE NOTE 7 ON PLANS FOR GFI PROTECTION
12. ELECTRICAL CONTRACTOR TO INSTALL PER PLANS & NEC