Permit: T08CM02680

Parcel: 13314456A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/22/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/21/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/19/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE ADEQUATE OVERCURRENT PROTECTION FOR FAN COILS AS PER DATA PLATES
2. PROVIDE DUCT SMOKE DETECTORS FOR ALL FAN COILS
3. DETECTORS MUST ALL BE TIED TOGETHER
4. PROVIDE AUDIBLE AND VISIBLE ALARMS
5. PROVIDE AIR BALANCE
6. STRAP FLEX DUCTS UP OFF OF GRID
7. SUPPORT DIFFUSERS
8. PROVIDE GFI SERVICE RECEPTACLES WITHIN 25' OF EQUIPMENT ON ROOF