Permit: T08CM02678

Parcel: 13317064B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/02/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
INSULATE NEW SPIRAL PIPE
WILL CHECK ON FINAL
11/24/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. REMOVE SHEETROCK FROM BATHROOM CEILING AND PROVIDE BACKING AROUND CEILING BOXES.
2. FLEX DUCTS STILL EXCEED 8'
3. OK PARTIAL CEILING TILES
11/21/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT FLEX DUCTS
2. SUPPORT DIFFUSERS
3. PROVIDE RETURN AIR TRANSFER IN ROOM 405
4. PROVIDE BACKING AROUND CEILING BOXES
5. SHORTEN THE FLEX DUCTS TO THE HALLWAY MAX. LENGTH ON FLEX DUCTS 8'