Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE AIR BALANCE OK OK FOR FINAL |
|
| 01/27/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNITS OVERFUSED CONDUIT STILL NOT SEALED |
|
| 01/26/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/23/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DUCT NOT SEALED IN WAREHOUSE AREA 2. SEAL ROOF JACKS AT UNIT ELECTRICAL 3. UNIT DATA PLATES NOT IDENTIFIED AT HEAT STRIPS 4. PROVIDE AIR BALANCE REPORT PER PLANS |