Permit: T08CM02673

Parcel: 132081770


Addresses:

1991 E AJO WY


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T08CM02673

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2009 FRAMING Approved IVRS - Inspection :*
PLAN REVISION 12/18/08
01/08/2009 FRAMING Partial Approval IVRS - Inspection :*
NO INSPECTION TRUCK BROKE DOWN
12/12/2008 FRAMING Partial Approval IVRS - Inspection :*
NEED REVISED PLAN AND RFI's
12/10/2008 FRAMING Partial Approval IVRS - Inspection :*
1. PLAN CALLS FOR 11 7/8 TJI CEILING JOIST
WILL NEED PLAN REVISION -- 2X8's USED NEED WET STAMPED RFI FROM ENGINEER
2. NEED RFI FOR SHOT PINS INSTEAD OF REDHEADS AT BOTTOM PLATE AND NO SLIP CLIPS USED
3. ALTERNATE WALL BRACING ON MEZZANINE
4. BACKING FOR HC BATHS AND TOILETS 16" TO 18" FROM FINISH WALL
5. SHEETROCK AT OWN RISK
6. BLOCKING NEEDED (2) ON A.3
7. NEED TO ADD SPRINKLER HEAD UNDER ENCLOSED STAIRWELL
12/09/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS -- DOOR LOCKED
ARRIVED @ 8:30 AM AS SCHEDULED W/CRAIG