Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02656
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/14/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PONY WALL IN RECEPTION AREA 2. OK TO ENERGIZE PANELS 3HB, 3HA |
|
04/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED REVISED PLANS FOR CHANGES TO DISTRIBUTION SYSTEM 2. MAIN BREAKER IN 3000A GEAR HAS TRIP UNIT RATED @ 2000A PLAN CALLS FOR 1600A TRIP UNIT 3. SHOULD DISTRIBUTION BOARD 2HDS HAVE MAIN BREAKER BASED ON NEC 225.30 4. OK TO ENERGIZE 2HDS AND 4HA |
|
04/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LID AND EAST WALL AT LOBBY ENTRANCE |
|
03/09/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
03/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
03/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK HARD LIDS RMS. 102, 106, 111 2. OK WALLS RMS. 102, 103, 122 |
|
02/10/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/09/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT RMS. 100, 101, 102, 103, 122, 121 |
|
12/04/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
12/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TOP OUT MASONRY WALLS |
|
12/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TOPOUT |
|
12/01/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
11/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST LIFT |