Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02656
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/14/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 04/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK PONY WALL IN RECEPTION AREA 2. OK TO ENERGIZE PANELS 3HB, 3HA |
|
| 04/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED REVISED PLANS FOR CHANGES TO DISTRIBUTION SYSTEM 2. MAIN BREAKER IN 3000A GEAR HAS TRIP UNIT RATED @ 2000A PLAN CALLS FOR 1600A TRIP UNIT 3. SHOULD DISTRIBUTION BOARD 2HDS HAVE MAIN BREAKER BASED ON NEC 225.30 4. OK TO ENERGIZE 2HDS AND 4HA |
|
| 04/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LID AND EAST WALL AT LOBBY ENTRANCE |
|
| 03/09/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK HARD LIDS RMS. 102, 106, 111 2. OK WALLS RMS. 102, 103, 122 |
|
| 02/10/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/09/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS EXCEPT RMS. 100, 101, 102, 103, 122, 121 |
|
| 12/04/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 12/03/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TOP OUT MASONRY WALLS |
|
| 12/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TOPOUT |
|
| 12/01/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1ST LIFT |