Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02655
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/15/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) STILL NEED INFO ON 2000 AMP BREAKER WITH 1600 AMP TRIP UNIT. PLEASE PROVIDE INFO 2) CHECK WITH BLDG INSPECTOR FOR TCO, I HAVE NO ISSUES |
|
| 07/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL PROTECTIVE BUSHING #4 OR LARGER 2) GEC CONDUCTOR TO TERMINATE AT MATERIAL BAR 3) INSTALL LABELS AT BREAKERS 4) MARK GROUNDS AND TERMINATE PROPERLY 5) GROUND RODS TO BE MINIMUM 6' APART 6) INSTALL COVER ON FIRE ALARM PANEL 7) PLAN CALLS FOR BREAKER AT SERVICE TO HAVE 1600 AMP TRIP UNIT, IT APPEARS EXISTING BREAKER HAS 2000 AMP TRIP UNIT |
|
| 07/13/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL WORK THEN CALL FOR FINAL |
|
| 07/10/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MISSING EXIT AT SOUTH DOORS 2) EM LIGHTS IN GYM NOT WORKING 3) MISSING OUTDOOR EM LIGHT SOUTH DOORS 4) WALK THRU OF EM LIGHTS ONLY |
|
| 07/09/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SOUTH ROOF MISSING SERVICE REPORT 2) NORTH ROOF GFI'S NOT WORKING 3) ELECTRICAL CONTRACTOR TO POWER CHECK RECEPTACLES 4) NEED BLANKS DEAD FRONT-PANEL DIRECTORIES 5) NOT A COMPLETE INSPECTION |