Permit: T08CM02655

Parcel: 14101008C


Addresses:

10770 E BILBY RD 02


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02655

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/28/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/15/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) STILL NEED INFO ON 2000 AMP BREAKER WITH 1600 AMP TRIP UNIT. PLEASE PROVIDE INFO
2) CHECK WITH BLDG INSPECTOR FOR TCO, I HAVE NO ISSUES
07/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL PROTECTIVE BUSHING #4 OR LARGER
2) GEC CONDUCTOR TO TERMINATE AT MATERIAL BAR
3) INSTALL LABELS AT BREAKERS
4) MARK GROUNDS AND TERMINATE PROPERLY
5) GROUND RODS TO BE MINIMUM 6' APART
6) INSTALL COVER ON FIRE ALARM PANEL
7) PLAN CALLS FOR BREAKER AT SERVICE TO HAVE 1600 AMP TRIP UNIT, IT APPEARS EXISTING BREAKER HAS 2000 AMP TRIP UNIT
07/13/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ALL WORK THEN CALL FOR FINAL
07/10/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MISSING EXIT AT SOUTH DOORS
2) EM LIGHTS IN GYM NOT WORKING
3) MISSING OUTDOOR EM LIGHT SOUTH DOORS
4) WALK THRU OF EM LIGHTS ONLY
07/09/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SOUTH ROOF MISSING SERVICE REPORT
2) NORTH ROOF GFI'S NOT WORKING
3) ELECTRICAL CONTRACTOR TO POWER CHECK RECEPTACLES
4) NEED BLANKS DEAD FRONT-PANEL DIRECTORIES
5) NOT A COMPLETE INSPECTION