Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02654
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/23/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* EM LIGHTING NEEDS TO BE OPERATIONAL |
|
06/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK REMAINDER OF PANELS FINISH ALL PREVIOUS INSPECTION ITEMS |
|
06/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED PROTECTIVE BUSHINGS ON CONDUCTORS #4 OR LARGER 2) GEC FOR X-FMR TO TERMINATE ON NEUTRAL 3) CHECK WATER BOND IS SIZED PROPERLY 4) NEED TO FINISH CHECING PANELS |
|
06/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK INTERIOR EM LIGHTS AND EXITS |
|
05/29/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED PANEL SCHEDULE TO SHOW EM CIRCUIT |
|
05/26/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* MINI-SPLIT OVERFUSED AND MISSING COVER OK REST OF ROOF |
|
05/20/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK POWER TO RECEPTACLES CLASS RMS AND HALLS EXCEPT RM. 319 |