Permit: T08CM02647

Parcel: 12705001D


Addresses:

660 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
03/23/2009 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
03/03/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
12/30/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
12/24/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE CABLES WITHIN 8" OF ENTERING OF PANEL
2. PROTECT CABLES AT TOP 300.4
3. BONDING JUMPER TO BE SIZED PER 250.66
4. USE ALL APPROVED PARTS WITH MAST SUPPORT
5. LUGS TO HAVE SURFACE CONTACT - ALSO, DO NOT STACK
6. TIGHTEN CONDUCTOR TERMINATIONS
7. LABEL PANELS, PERMANENT METAL LABELING
8. REMOVE BOND LINK AT NEUTRAL AND BOND
ENCLOSURE PNL "A"
9. TEP REQUIRES 24" OUT AT WEATHERHEAD
10. FINISH DRIVING GROUND ROD (LAST INSP.)
11. GROUNDING NOT AS PER PLANS
12. PLANS CALL FOR CONDUIT PROVIDE LETTER FOR MC CABLE