Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/03/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 12/30/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 12/24/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SECURE CABLES WITHIN 8" OF ENTERING OF PANEL 2. PROTECT CABLES AT TOP 300.4 3. BONDING JUMPER TO BE SIZED PER 250.66 4. USE ALL APPROVED PARTS WITH MAST SUPPORT 5. LUGS TO HAVE SURFACE CONTACT - ALSO, DO NOT STACK 6. TIGHTEN CONDUCTOR TERMINATIONS 7. LABEL PANELS, PERMANENT METAL LABELING 8. REMOVE BOND LINK AT NEUTRAL AND BOND ENCLOSURE PNL "A" 9. TEP REQUIRES 24" OUT AT WEATHERHEAD 10. FINISH DRIVING GROUND ROD (LAST INSP.) 11. GROUNDING NOT AS PER PLANS 12. PLANS CALL FOR CONDUIT PROVIDE LETTER FOR MC CABLE |