Permit: T08CM02643

Parcel: 138071030

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/16/2009 BUILDING - FINAL Approved IVRS - Inspection :*
01/15/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) WORK NOT COMPLETE ENOUGH TO INSPECT
01/09/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOTES 2 & 8 FROM PREVIOUS
2) HOUSE NOT INSULATED
01/08/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY VICTORIA
01/06/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) A/C UNIT OVER FUSED 45 MAX
2) GFCI PROTECT SERVICE 110 ON ROOF TOP WITH WEATHERED COVER
3) GROUND ROD SYSTEM AND BOND NEW PANEL
4) 2-20 AMP CIRCUITS REQUIRED KITCHEN
5) NEW WATER HEATER REQUIRES COMBUSTION RELIEF 100 CU INCH AND DRIP LEG
6) GROUND ALL METAL BOXES/INSTALL PROPER ROMEX CONNECTORS THROUGHOUT
7) SECURE ALL ROMEX 8" FROM BOX
8) ROMEX INSULATION MUST TERMINATE IN BOX
9) INSTALL APA SHUT OFF AT STOVE VALVE
10) INSTALL HARD WIRED SMOKE DETECTORS THROUGHOUT, MISSING IN HALLWAY AND UNPERMITTED ROOM
11) PROVIDE ATTIC ACCESS EXISTING HOUSE
12) CEILING FAN BOXES REQUIRED TOTAL REMODEL INTERIOR
13) PROVIDE ACCESS TO ATTIC
14) REFEE TO APPLY NEXT DENIAL
12/31/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE HOME
2) HOUSE LOCKED
3) PLEASE CALL FOR RE-INSPECTION
12/19/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
12/17/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
12/16/2008 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
12/15/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/07/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE FOOTERS TO VERIFY DEPTH
2. EXPOSE BOTTOM PLATES TO VERIFY TREATED PLATES
3. EXPOSE ALL ELECTRICAL COVERED W/O INSPECTION OR PROVIDE APPROVED LETTERHEAD FROM LICENSED ELECTRICIAN STATING ALL WORK DONE TO CODE VERIFY GROUNDING TO ADDITION
4. PROVIDE ACCESS TO ATTIC
5. PROVIDE ACCESS TO ROOF TOP UNIT
6. PROVIDE GAS PRESSURE TEST
7. PANEL SCHEDULE DOES NOT MATCH
8. FLOOR PLAN DOES NOT SHOW CLOSET

STOPPED INSPECTION

IF TO BE USED AS BEDROOM WINDOW SILL HEIGHT ABOVE 44"