Permit: T08CM02615

Parcel: 132166300

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/09/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH ITEMS #3; ROOF: 1, 3
2. ALL STRANDS TO BE UNDER TERMINAL SCREWS
06/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES 314.20
2. NEED DISCONNECTING MEANS FOR OVERHEAD DOOR MOTORS
3. WAREHOUSE LIGHTING CONTROLS NOT AS PER PLANS

ROOF:
1. MAINTAIN WORKING CLEARANCES - 110.26
2. PROPERLY MOUNT BELL BOXES
3. LABEL DISCONNECTS
4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR
5. ONLY ONE CONDUCTOR TO GROUND SCREW
6. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8
06/01/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ISOLATED GROUND TO BE TO SERVICE-FLOATING IN PANEL