Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH ITEMS #3; ROOF: 1, 3 2. ALL STRANDS TO BE UNDER TERMINAL SCREWS |
|
| 06/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES 314.20 2. NEED DISCONNECTING MEANS FOR OVERHEAD DOOR MOTORS 3. WAREHOUSE LIGHTING CONTROLS NOT AS PER PLANS ROOF: 1. MAINTAIN WORKING CLEARANCES - 110.26 2. PROPERLY MOUNT BELL BOXES 3. LABEL DISCONNECTS 4. CORRECTLY IDENTIFY UNGROUNDED CONDUCTOR 5. ONLY ONE CONDUCTOR TO GROUND SCREW 6. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8 |
|
| 06/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ISOLATED GROUND TO BE TO SERVICE-FLOATING IN PANEL |