Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/17/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/13/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/10/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL TRADES 2) OVERKNOTCHED 6 X 12 AT MASONRY ? POCKET MUST BEAR 1 1/2" MINIMUM. 3) MISSING CS20 STRAP PER PLAN 4) EXPOSE H2.5 CLIP AT 4 X 6 TO 6 X 12 CONNECTION 5) NAIL OSB AT HOLDOWNS TO TOP PLATE 6" ON CENTER 6) MISSING OSB CANNOT STRIP PER PLAN 7) STRAP BEAM AT CARPORT TO STORAGE ROOM EAST WALL |