Permit: T08CM02601

Parcel: 14042075D


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/22/2010 FIRE - FINAL Approved Fire doors tested all fully closed and latched.
12/15/2009 FIRE - FINAL Partial Approval SAME LAST INSPECTION
12/14/2009 FIRE - FINAL Partial Approval Temp C of O approved for occupation.
Will need to repair or replace fire doors in hallways not working properly. Can screw shut small door (17 ½") and leave large door operational this will be ok for temp C of O. Contractor stated they are going to change all fire doors with 4' wide single doors, after replacing doors and pass operational testing then final C of O fire approval will be given.
11/30/2009 FIRE - FINAL Partial Approval TEMP C OF O APPROVED FOR TRAINING ONLY!!! NO OVERNIGHT SLEEPING.
1. FIRE DOORS SHALL OPERATED PROPERLY, ALL DOORS FAILED DURING ALARM TESTING.

2. REPAIR SPRINKLER HEADS ON 3RD FLOOR IN ROOMS 342 & 343 HOUSEKEEPING AND MECH. ROOM. ONE HEAD BLOCKED BY LIGHT AND ONE HEAD COVERED.
3. RELABEL STAIRWELL #4 AS #3 LABEL WRONG.