Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2010 | FIRE - FINAL | Approved | Fire doors tested all fully closed and latched. | |
| 12/15/2009 | FIRE - FINAL | Partial Approval | SAME LAST INSPECTION | |
| 12/14/2009 | FIRE - FINAL | Partial Approval | Temp C of O approved for occupation. Will need to repair or replace fire doors in hallways not working properly. Can screw shut small door (17 ½") and leave large door operational this will be ok for temp C of O. Contractor stated they are going to change all fire doors with 4' wide single doors, after replacing doors and pass operational testing then final C of O fire approval will be given. |
|
| 11/30/2009 | FIRE - FINAL | Partial Approval | TEMP C OF O APPROVED FOR TRAINING ONLY!!! NO OVERNIGHT SLEEPING. 1. FIRE DOORS SHALL OPERATED PROPERLY, ALL DOORS FAILED DURING ALARM TESTING. 2. REPAIR SPRINKLER HEADS ON 3RD FLOOR IN ROOMS 342 & 343 HOUSEKEEPING AND MECH. ROOM. ONE HEAD BLOCKED BY LIGHT AND ONE HEAD COVERED. 3. RELABEL STAIRWELL #4 AS #3 LABEL WRONG. |