Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/03/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/19/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SMOKE/FIRE DAMPERS TESTED OK ALL FLOORS 2) INSTALL CONDENSATE PIPING PER MANUFACTURERS INSTALLATION INSTRUCTIONS |
|
| 11/18/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/16/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONDENSATE PIPING NOT COMPLETE 2) SUPPORT FLUE PIPING ON HORIZONTAL UNITS 3) PROVIDE ALL BUSHINGS ON HORIZONTAL UNITS 4) CONDENSATE NOT PROPERLY INSTALLED ON HORIZONTAL UNITS 5) 3RD FLOOR SMOKE DAMPER INSPECTION FAILED 6) THIS INSPECTION IS NOT COMPLETE ONLY LOOKED AT 3RD FLOOR |
|
| 10/27/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* |