Permit: T08CM02601

Parcel: 14042075D


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
08/07/2009 MECHANICAL - PROGRESS Approved IVRS - Inspection :*
1) N.E., 2 N.E., 3 N.E. OK
2) N.W., 2 N.W., 1 N.W. OK
3) OK TO COVER DUCT CHASE N. OF BLDG ( X2)
08/04/2009 MECHANICAL - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEXT FAILED INSPECTION WILL RESULT IN A REFEE
07/31/2009 MECHANICAL - PROGRESS Not ready for Inspection IVRS - Inspection :*
06/25/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
06/23/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
1. NORTHWEST CORNER - DO NOT COVER CHASE
2. NORTHEAST CORNER - DO NOT COVER CHASE
06/08/2009 MECHANICAL - PROGRESS Not ready for Inspection IVRS - Inspection :*
1. PROVIDE APPROVED ACCESS TO UNITS
2. INSULATE EXHAUST PIPING AS REQUIRED
3. INSTALL FIRE DAMPERS IN APPROVED MANNER
4. PROVIDE SUBMITTALS ON FIRE DAMPERS BEING USED
05/27/2009 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
05/26/2009 MECHANICAL - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL DUCT TO BE SEALED WITH MASTIC, TAPE NOT ACCEPTABLE
2. ALL DUCT JOINTS TO BE MECHANICALLY FASTENED MIN. 3 SCREWS PER JOINT
3. PROVIDE PROPER FIRE RATING AT CHASES
4. VERIFY FIRE DAMPERS AT CHASE TO ATTIC SPACE