Permit: T08CM02601

Parcel: 14042075D


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) RECEIVED OUTDOOR LIGHTING CODE LETTER
2) CHAFING DISH REMOVED
3) OK ELECTRIC
12/15/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) FOUNTAIN BONDING CANNOT USE SHEET METAL THREADED SCREWS 250.8
2) METAL OUTDOOR PULL BOX COVERS TO BE GROUNDED
3) GROUNDING FOR SATELLITE DISH TO BE PER 810.15 & 810.21
4) SUPPORT RACEWAY CONTAINING COAX CABLES
5) PREVENT ENTRANCE OF WET WEATHER TO RACEWAY FOR COAX
6) FINISH PREVIOUS ITEMS FOR A/C SPLIT SYSTEMS, ATTIC WALKWAYS, POOL, A/C'S, CHAFING DISH, OUTDOOR PHONE AND OUTDOOR LIGHTING
12/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/04/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1st FLOOR:
1. EXPOSED NM CABLE - MEETING ROOM
2. FINISH MECHANICAL ROOM
3. NEED DISCONNECTS FOR A/C/ SPLIT SYSTEM
4. VERTICAL EXIST SIGNS
5. LISTING CHAFFING HEATERS
OK COMMON AREAS 2ND FLOOR, 1ST FLOOR EXCEPT OFFICES.
OK HANDICAP EQUIPMENT 1ST & 2ND FLOORS
OK LABELING REQUIPMENT

2ND FLOOR:
1. FINISH PANEL LABELING
2. NEED DISCONNECTS FOR A/C SPLIT SYSTEM
12/02/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/01/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) LIGHTS FOR EM FLOODS NOT WORKING, GUEST LAUNDRY AND FITNESS
11/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK MAKE UP AND WIRING COMMERCIAL WASHERS AND DRYERS
2) FINISH LABELING OF DICONNECTS
11/18/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
3RD FLOOR:
1) DISCONNECTING MEANS FOR FIXTURES IN NON-DWELLING AREAS 410.63
2) CONTRACTORS TO BE LISTED
OUTDOOR:
1) SPLICES TO BE FOR WET LOCATION
2) OK 3 POLES SOUTHWEST
11/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE VERIFY CORD AND PLUG CONNECTIONS FOR COMERCIAL WASHERS AND DRYERS
2) VERIFY LISTING LABELS COMMERCIAL DRYERS
3) FINISH PANEL SCHEDULES
4) FINISH HANDICAP DEVICES
5) OK 1ST FLOOR DWELLING UNITS (ONLY), EXCEPT AS NOTED
6) DO NOT OCCUPY HOTEL WITH OTHER THAN CONSTRUCTION PERSONEL
11/10/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/09/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/23/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/21/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK CORRIDOR 271 ABOVE CEILING
2) OK DEVICES AND LIGHTS GUEST ROOMS OFF OF CORRIDOR 252 & 271
3) FINISH APPLIANCES, FIRE ALARMS AND PANELS
09/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/15/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK DEVISES & LIGHS GUEST ROOMS OFF OF BACK DOOR, 352, 371 EXCEPT AS N?
1. FILL UNUSED OPENING IN BACK OF FIXTURE
2. ? APPLIANCES, FIRE ALARMS & ?