Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) RECEIVED OUTDOOR LIGHTING CODE LETTER 2) CHAFING DISH REMOVED 3) OK ELECTRIC |
|
| 12/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) FOUNTAIN BONDING CANNOT USE SHEET METAL THREADED SCREWS 250.8 2) METAL OUTDOOR PULL BOX COVERS TO BE GROUNDED 3) GROUNDING FOR SATELLITE DISH TO BE PER 810.15 & 810.21 4) SUPPORT RACEWAY CONTAINING COAX CABLES 5) PREVENT ENTRANCE OF WET WEATHER TO RACEWAY FOR COAX 6) FINISH PREVIOUS ITEMS FOR A/C SPLIT SYSTEMS, ATTIC WALKWAYS, POOL, A/C'S, CHAFING DISH, OUTDOOR PHONE AND OUTDOOR LIGHTING |
|
| 12/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1st FLOOR: 1. EXPOSED NM CABLE - MEETING ROOM 2. FINISH MECHANICAL ROOM 3. NEED DISCONNECTS FOR A/C/ SPLIT SYSTEM 4. VERTICAL EXIST SIGNS 5. LISTING CHAFFING HEATERS OK COMMON AREAS 2ND FLOOR, 1ST FLOOR EXCEPT OFFICES. OK HANDICAP EQUIPMENT 1ST & 2ND FLOORS OK LABELING REQUIPMENT 2ND FLOOR: 1. FINISH PANEL LABELING 2. NEED DISCONNECTS FOR A/C SPLIT SYSTEM |
|
| 12/02/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 12/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) LIGHTS FOR EM FLOODS NOT WORKING, GUEST LAUNDRY AND FITNESS |
|
| 11/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK MAKE UP AND WIRING COMMERCIAL WASHERS AND DRYERS 2) FINISH LABELING OF DICONNECTS |
|
| 11/18/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/17/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 3RD FLOOR: 1) DISCONNECTING MEANS FOR FIXTURES IN NON-DWELLING AREAS 410.63 2) CONTRACTORS TO BE LISTED OUTDOOR: 1) SPLICES TO BE FOR WET LOCATION 2) OK 3 POLES SOUTHWEST |
|
| 11/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY CORD AND PLUG CONNECTIONS FOR COMERCIAL WASHERS AND DRYERS 2) VERIFY LISTING LABELS COMMERCIAL DRYERS 3) FINISH PANEL SCHEDULES 4) FINISH HANDICAP DEVICES 5) OK 1ST FLOOR DWELLING UNITS (ONLY), EXCEPT AS NOTED 6) DO NOT OCCUPY HOTEL WITH OTHER THAN CONSTRUCTION PERSONEL |
|
| 11/10/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 11/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/09/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 10/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/21/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK CORRIDOR 271 ABOVE CEILING 2) OK DEVICES AND LIGHTS GUEST ROOMS OFF OF CORRIDOR 252 & 271 3) FINISH APPLIANCES, FIRE ALARMS AND PANELS |
|
| 09/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 09/15/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK DEVISES & LIGHS GUEST ROOMS OFF OF BACK DOOR, 352, 371 EXCEPT AS N? 1. FILL UNUSED OPENING IN BACK OF FIXTURE 2. ? APPLIANCES, FIRE ALARMS & ? |