Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2009 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 12/15/2009 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 12/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* COMM ROOM: 1) A/C DISCONNECT SPLIT SYSTEM AND FINISH PANEL LABELING ATTIC: 1) WALK WAY TO EXTEND FROM POINT OF ENTRANCE TO SERVICE DISCONNECT-SUPPORT 'T' STAT CABLES 725.24 POOL: 1) RECEPT COVER TO BE WEATHER PROOF, WETHER OR NOT PLUGGED INTO 406.6 |
|
| 12/04/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 12/03/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/02/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/01/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/19/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/18/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) CHAFEING HEATERS ARE ONLY RECOGNIZED AS COMPONENTS NOT LISTED AS EQUIPMENT 2) WILL NEED OUTDOOR LIGHTING REVIEW PER OUTDOOR LIGHTING CODE 3) OK TO MAIN AT POOL PANEL 4) OK SUB PANELS MAKE UP 5) OK FITNESS EQUIPMENT 6) OK KITCHEN EQUIPMENT EXCEPT AS NOTED 7) OK ELEVATORS TO MAINS (X2) |
|
| 11/17/2009 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL A/C UNITS TO MATCH DISCONNECTS 2) ALL METAL WITHIN 5' OF FOUNTAIN TO BE BONDED PER ART. 680 3) OUTDOOR PHONES TO BE FOR WET LOCATIONS 4) SPLIT SYSTEM A/C INTERIOR UNITS NEED DISCONNECTING MEANS AND CORDS NOT ALLOWED FOR WIRING METHODS IN WALLS 5) OUTDOOR DISCONNECTS OK |
|
| 11/16/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/13/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/10/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/05/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/27/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/29/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/21/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/17/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/15/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK 2ND FLOOR CORRIDOR 252 ABOVE CEILING 2) OK DEVICES AND LIGHTS GUEST ROOMS CORRIDOR 341 3) FINISH APPLIANCES, FIRE ALARM AND PANELS |
|
| 09/14/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 09/08/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* NOTE: 1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 2) SUPPORT VDV CABLING 725.24,760.24 & 800.24 3) OK ELECTRIC-EXCEPT AS NOTED CORRIDOR 341,352 AND 371 |
|
| 09/01/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/06/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/24/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/15/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK RACEWAY FOR POOL FEEDER PER 680 2) OK JUNCTION BOX WITH FEEDER HALLWAY #171 3) OK PVC POLE TO POLE AS MARKED |
|
| 07/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/30/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/29/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/22/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/15/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/01/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/21/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/18/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/15/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/06/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1. USE APPROVED HARDWARE TO HANG SERVICE NOT DRYWALL SCREWS 2. LABEL BREAKERS 3. WHERE DOES 60A FEEDER GO TO PLEASE HAVE ELECTRICIAN ON SITE TO ANSWER QUESTIONS |
|
| 04/09/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |