Permit: T08CM02601

Parcel: 14042075D


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/16/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK INTERIOR WALLS
2) OK 2ND FLOOR, EXCEPT AS NOTED-ROOM DWELLING
2ND FLOOR:
1) FINISH PANEL SCHEDULES
2) WAITING ON HANDICAP DEVICES
OUTDOOR ENCLOSURE:
1) PROTECT LB AND RACEWAYS FROM PHYSICAL DAMAGE
10/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MAKE UP AND 320 WATTS ON LIGHT POLE-OK
2) MAKE UP AND 150 WATTS ON LIGHT POLE-OK
10/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/23/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK DEVICES AND LIGHTS GUEST ROOMS OFF OF CORRIDOR 241 AND FIRE ALARMS, EXCEPT 209
2) FINISH APPLIANCES AND PANELS
3) FINISH FIRE ALARM-210
4) OK CANS IN SOFFITS ROOM 164
09/01/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR:
1) FINISH FIRE ALARM
2) OK ELECTRIC ABOVE CEILING #341
GREAT ROOM 150:
1) OK CANS IN CEILING
08/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BLDG INSPECTOR TO VERIFY FIRE STOPPING FOR SEPERATION
2) OK ROOMS 166-168,170 SUBJECT TO FIRE STOPPING
08/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NM CABLE NOT ALLOWED ABOVE DROPPED OR SUSPENDED CEILINGS PER 334.12 (A) (2)
2) REMOVE INSULATION TO INSPECT ROOMS
3) OK ROOMS 142,143,147-149, 152-157, 159-165, 169, 173-176
07/24/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
07/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2ND AND 3RD FLOOR PANELS MAKE UP
2) OK 1 ENTRY TO PAVILLION UNDERGROUND-OTHERS NOT ALLOWED CONTRACTOR TO NM CABLE REST OF STRUCTURE
3) OK ROOMS 145-146
07/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) POOL FEEDER PER 680.25 (A)
2) OK ROOM 255, 154 AND 174
3) OK 1ST FLOOR DWELLING UNIT ROUGH ELECTRIC AND PANELS
06/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNDERGROUND AT PAVILLION NOT APPROVED, GENERAL AND ELECTRICAL CONTRACTORS TO PROVIDE AN ACCEPTABLE SOLUTION
PANELS 3RD FLOOR:
1) USE MANUFACTURERS HOLDOWN ON LUG ADAPTOR
2) UNDERGROUND CONDUCTORS TO BE MARKED ENTIRE LENGTH
3) REVERSE FEED THRU FLOW AT PANEL-ROOM 305
06/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOMS 342, 343, 355, 370, 373, 374, 377
06/05/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROOM 217-234, 236, 238
OK 2ND FLOOR CORRIDOR WALLS
06/01/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SECURE CABLES TO BOXES 312.5
2. BUILDING INSPECTOR TO VERIFY FIRE STOPPING
3. OK ROUGH ELECTRIC ROOMS 200-216, 218, 220
OK STAIRWELL #4
05/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR: OK UNITS 300-316, 318, 320
OK STAIRWELL 340, 344

1ST FLOOR: OK DEMISING WALL MAIN ELECTRIC ROOM 146
05/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNITS 309-320
1. NM AND SE CABLES NOT ALLOWED CORRIDOR
2. VDV CABLE NEED TO BE SUPPORTED IN WALL 725.24, 800.24
3. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING
4. RECEPTACLE BACK TO BACK
5. HAVE BUILDING INSPECTOR VERIFY PANELS IN FIRE WALLS
04/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FINISH VDV CABLING AS PER 725.24, 800.24
2. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING
3. NO PANELS AT THIS TIME
4. VERIFY WEIGHT OF WALL LIGHTS --
SINGLE GANG BOX UP TO 6 LBS.