Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK INTERIOR WALLS 2) OK 2ND FLOOR, EXCEPT AS NOTED-ROOM DWELLING 2ND FLOOR: 1) FINISH PANEL SCHEDULES 2) WAITING ON HANDICAP DEVICES OUTDOOR ENCLOSURE: 1) PROTECT LB AND RACEWAYS FROM PHYSICAL DAMAGE |
|
| 10/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MAKE UP AND 320 WATTS ON LIGHT POLE-OK 2) MAKE UP AND 150 WATTS ON LIGHT POLE-OK |
|
| 10/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/23/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK DEVICES AND LIGHTS GUEST ROOMS OFF OF CORRIDOR 241 AND FIRE ALARMS, EXCEPT 209 2) FINISH APPLIANCES AND PANELS 3) FINISH FIRE ALARM-210 4) OK CANS IN SOFFITS ROOM 164 |
|
| 09/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR: 1) FINISH FIRE ALARM 2) OK ELECTRIC ABOVE CEILING #341 GREAT ROOM 150: 1) OK CANS IN CEILING |
|
| 08/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BLDG INSPECTOR TO VERIFY FIRE STOPPING FOR SEPERATION 2) OK ROOMS 166-168,170 SUBJECT TO FIRE STOPPING |
|
| 08/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NM CABLE NOT ALLOWED ABOVE DROPPED OR SUSPENDED CEILINGS PER 334.12 (A) (2) 2) REMOVE INSULATION TO INSPECT ROOMS 3) OK ROOMS 142,143,147-149, 152-157, 159-165, 169, 173-176 |
|
| 07/24/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2ND AND 3RD FLOOR PANELS MAKE UP 2) OK 1 ENTRY TO PAVILLION UNDERGROUND-OTHERS NOT ALLOWED CONTRACTOR TO NM CABLE REST OF STRUCTURE 3) OK ROOMS 145-146 |
|
| 07/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) POOL FEEDER PER 680.25 (A) 2) OK ROOM 255, 154 AND 174 3) OK 1ST FLOOR DWELLING UNIT ROUGH ELECTRIC AND PANELS |
|
| 06/30/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND AT PAVILLION NOT APPROVED, GENERAL AND ELECTRICAL CONTRACTORS TO PROVIDE AN ACCEPTABLE SOLUTION PANELS 3RD FLOOR: 1) USE MANUFACTURERS HOLDOWN ON LUG ADAPTOR 2) UNDERGROUND CONDUCTORS TO BE MARKED ENTIRE LENGTH 3) REVERSE FEED THRU FLOW AT PANEL-ROOM 305 |
|
| 06/29/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 06/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOMS 342, 343, 355, 370, 373, 374, 377 |
|
| 06/05/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROOM 217-234, 236, 238 OK 2ND FLOOR CORRIDOR WALLS |
|
| 06/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SECURE CABLES TO BOXES 312.5 2. BUILDING INSPECTOR TO VERIFY FIRE STOPPING 3. OK ROUGH ELECTRIC ROOMS 200-216, 218, 220 OK STAIRWELL #4 |
|
| 05/21/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3RD FLOOR: OK UNITS 300-316, 318, 320 OK STAIRWELL 340, 344 1ST FLOOR: OK DEMISING WALL MAIN ELECTRIC ROOM 146 |
|
| 05/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* UNITS 309-320 1. NM AND SE CABLES NOT ALLOWED CORRIDOR 2. VDV CABLE NEED TO BE SUPPORTED IN WALL 725.24, 800.24 3. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING 4. RECEPTACLE BACK TO BACK 5. HAVE BUILDING INSPECTOR VERIFY PANELS IN FIRE WALLS |
|
| 04/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING AS PER 725.24, 800.24 2. HAVE BUILDING INSPECTOR VERIFY FIRE STOPPING 3. NO PANELS AT THIS TIME 4. VERIFY WEIGHT OF WALL LIGHTS -- SINGLE GANG BOX UP TO 6 LBS. |