Permit: T08CM02601

Parcel: 14042075D


Addresses:

2705 E EXECUTIVE DR

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/16/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
11/16/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
11/05/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
3RD FLOOR:
1) FINISH PANEL LABELING
2) FINISH KITCHEN 326
3) WAITING ON HANDICAP DEVICES
4) OK DWELLING ROOMS, EXCEPT AS NOTED
5) OK ACROSS PARKING LOT AND ENTRY DRIVE SOUTH SIDE
10/28/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. FOR POLE LIGHTS EAST AND WEST END OF PARKING LOT
10/09/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK CORRIDOR LIGHTS 1ST, 2ND AND 3RD FLOORS
2) OK 16 POLE BASES
3) FINISH SOUTHWEST 3 BASES
4) FOUNTAIN TO BE PER 680.6 PART I ALSO, PART II
10/07/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) VERIFY BONDING INSPECTION FOR FOUNTAIN ART. 680, ALSO ANY UNDERGROUND INSTALLED
2) PROTECT CONDUCTORS FOR SERVICE LATERALS 356.42 AND 300.4
3) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT
4) OK FRONT COUNTER, OK PVC CONDUIT TO J-BOX BOLLARDS, OK GUEST ROOMS, OFFICE CORRIDOR 152 & 171 AND OK ABOVE CEILING #141, 152 AND 171
5) RECEIVED LETTER OF TORQUE
09/14/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/24/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1 1/4" PVC POOL TO BLDG
2) OK TO TAPE SPLICES AT GUTTERS
3) OK PAVILLION ROUGH
07/15/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/09/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
06/30/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
06/29/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
06/15/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS POLE TO POLE AND BOLLARD TO BOLLARD
AND BACK TO BUILDING AT COURTYARD

1. PAVILLION CONDUITS DENIED - COVERED WITHOUT INSPECTION
03/10/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK EAST WING BELOW SLAB INSIDE
03/04/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK SECONDARYS U.G. CONDUITS AND 2 1/2" FOR TEMP
2. VERIFY USE OF ROMEX THRU ARCH

6 FEEDER CALC - 6 UNITS
79500VA
44% 34980
02/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK BELOW SLAB CONDUITS FOR ELEVATOR AND FLOOR BOXES
LOBBY MAIN ENTRANCE AREA