Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T08CM02598
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
08/05/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ONLY ONE ? NOT ALLOWED ON STREAM OF P TRAP: VERTICAL EXTENSIONS ARE NOT FOR USE ON TRAP ARM 2) EXPOSE CLEANOUTS 3) RUN TEST FIXTURES 4) CORRECTIONS AT WATER HEATER |
|
08/04/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) BEVERAGES AND BACKFLOW CERTS NOT COMPLETE 2) ? OF TRAP CANNOT BE BELOW POINT OF VENT 3) VENT FITTING AT 3 COMP SINK IS IN BACKWARDS 4) ALL FITTINGS SHALL BE INSTALLED IN CORRECT DIRECTION OF FLOW 5) EXPANSION TANK REQUIRES SUPPORT WHEN FLEX CONNECTION IS USED AT WATER HEATER 6) A FLEX MAY NOT BE USED ON T & P 7) A VACUUM RELIEF VALVE IS REQUIRED WHEN WATER HEATER IS ABOVE FIXTURES 8) PLUG FLOOR SINK NOT IN USE |