Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T08CM02598
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
07/28/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) HS AND FS OK TO COVER 2) TEST AT KIT OK 3) RECONNECT DRAIN DOWNSTREAM OF GT 4) PROVIDE PROPER ALIGNMENT OF FITTINGS 5) CHECK VENT LAYOUT AT KS 6) SEE CODE SECTIONS AND DIAGRAMS PROVIDED 7) OK TO COVER WALL |
|
07/27/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SLOPE AT HS VENT FITTING IN BACKWARDS AT FS 2) NO VENT ALLOWED BETWEEN FC AND GT 3) STUB VENTS OUT AS HIGH AS POSSIBLE TO ENSURE THAT YOU HAVE ENOUGH ROOM TO MAKE CONNECTION AT FINAL |
|
07/24/2009 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AT HS AND FS; NOT PER PLAN OR UPC WET VENTING REQUIREMENTS 908.2 2) BACK PITCH AT TIE IN 3) SOLVENT WELD TEST FITTINGS REQUIRED IN CONCEALED LOCATIONS 4) DEMO OR COVER 5) FHA STRAPS MISSING 6) HYDRO MECH INTERCEPTOR (GT) REQUIRES A VENT ON STREAM, AS SHOWN ON PLAN 7) ALSO THE DIRECTLY CONNECTED SINK COMPARTMENTS ARE REQUIRED TO BE TRAPPED AND VENTED 8) FLOW CONTROL IS INSTALLED AFTER FIXTURE VENT SO THAT NO SYSTEM VENT IS INSTALLED BETWEEN FC AND GT INLET |