Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 10/17/2008 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 08/25/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MINIMUM FUSE SIZE 38 AMPS 2) CONDENSATE DRAIN NEED POSITIVE PITCH 3) SECURE GFI RECEPTACLE 4) GFI RECEPTACLE CANNOT BE DBL LUGGED TO A/C FEED 5) GAS TEST GAUGE STUCK AT 6 PSI-NO PRESSURE ON SYSTEM |