Date Description Inspector Results Comments
03/26/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED BACTERIA REPORT FOR POTABLE WATER AND OK FROM JM ARCHITECT FOR MIXING VALVE FOR ENTIRE HOT SYSTEM
03/16/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
REMOVE PVC AT WATER SERVICE
PROVIDE MIXING VALVE PER PLAN
SEE NOTE ABOUT NEW WH
03/03/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PER NOTE 19 ON P-1 INSTALL EXPANSION TANK AT WATER HEATER
2. HOSE BIBS REQUIRE ATMOSPHERIC VACUUM BREAKERS
3. STERILIZE WATER SYSTEM AND PROVIDE CLEAN BACTERIA REPORT