Permit: T08CM02581

Parcel: 123151140

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02581

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/16/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BATH LIGHT NEEDS A BOX - OUTLET HAS READINGS OF POWER
03/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CLEAN OR REPLACE DEVICES WITH EXCESS PAINT 110.12
2. BOXES MORE THAN 1/4" BOX TO SURFACE - 314.20
3. BATH LIGHT RECEPTACLE TO BE GFI PROTECTED
4. GROUND FIXTURE HARDWARE
5. KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI PROTECTED
6. REVISE CIRCUIT DIRECTORY PER 408.4
7. EM LIGHTING TO BE ON CIRCUIT SERVED 700.12 (E)