Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02581
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH |
|
12/16/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT NM CABLE AT STUDS -- 300.4 2. SUPPORT NM ON VERTICALS 3. GROUND METAL BOXES 4. USE APPROVED SPLICE CONNECTORS ALL CONDUCTORS 5. OPEN COVERED AREAS TO INSPECT - DEPTH AT BLOCK COVERED WALLS AND SOFFITS 6. CONNECT ALL GROUNDS |