Permit: T08CM02578

Parcel: 11710075B


Addresses:

270 N CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02578

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLAN CALLS FOR OCCUPANCY SENSORS
NEED TO INSTALL OR REVISE PLANS THEN SEND
THROUGH PLAN CHECK
03/05/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE ALL PREVIOUS INSPECTION ITEMS
INSTALL PER PLANS AND NEC
03/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. IDENTIFY EQUIPMENT GROUND FOR PANEL
2. NEED UPDATED PANEL DIRECTORY
3. FINISH WORK
4. NEED BOX EXTENSIONS BOXES MORE THAN 1/4" BACK
5. SOME RECEPTS HAVE NO POWER
6. NEED DISCONNECTING MEANS FOR AIR HANDLER IN TELEPHONE CLOSET
7. MISSING EM LIGHTS ENSURE CIRCUITED PER PLANS
8. MISSING OCCUPANCY SENSORS PER PLAN
9. MARK "SERVICE DISCONNECT"
10. SECURE DISCONNECT ON ROOF
11. NEED SERVICE RECEPT FOR CONDENSING UNIT WITHIN 25'