Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02578
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLAN CALLS FOR OCCUPANCY SENSORS NEED TO INSTALL OR REVISE PLANS THEN SEND THROUGH PLAN CHECK |
|
03/05/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE ALL PREVIOUS INSPECTION ITEMS INSTALL PER PLANS AND NEC |
|
03/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY EQUIPMENT GROUND FOR PANEL 2. NEED UPDATED PANEL DIRECTORY 3. FINISH WORK 4. NEED BOX EXTENSIONS BOXES MORE THAN 1/4" BACK 5. SOME RECEPTS HAVE NO POWER 6. NEED DISCONNECTING MEANS FOR AIR HANDLER IN TELEPHONE CLOSET 7. MISSING EM LIGHTS ENSURE CIRCUITED PER PLANS 8. MISSING OCCUPANCY SENSORS PER PLAN 9. MARK "SERVICE DISCONNECT" 10. SECURE DISCONNECT ON ROOF 11. NEED SERVICE RECEPT FOR CONDENSING UNIT WITHIN 25' |