Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2008 | ELECTRIC - FINAL | Approved | ||
| 09/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CANNOT USE FLEXIBLE CORD FOR PERMANENT WIRING METHOD |
|
| 09/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE ITEM #5 FROM PREVIOUS INSPECTION |
|
| 09/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS PANEL 2. INSTALL PROTECTIVE BUSHING ON FEEDER CONNECTORS 3. HAVE CUT STRANDS ON GROUND 4. PANEL CANNOT BE RECESSED MORE THAN 1/4" 5. PROVIDE INSTRUCTIONS FOR INSTANT HOT TO VERIFY IT CAN BE CORD & PLUG CONNECTED. PLAN CALLS FOR HARDWIRE WITH LOCK OUT ON BREAKER. SEE NEC 422 6. INSTALL EMT ON ROOF IN NEAT & WORKMANLIKE MANNER USE PROPER BENDS, BLOCKING TO BE SECURED TO ROOF 7. VERIFY SCREWS USE FOR STRAPPING ON ROOF ARE CORROSION PROOF 8. JUNCTION BOX ON ROOF NOT SIZED PROPERLY NEC 314.28 9. UNCHECK DISCONNECT 10. VERIFY NEW FEEDER CONDUCTOR SIZE WITH ENGINEER |