Permit: T08CM02566

Parcel: 133180080


Addresses:

7078 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02566

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2008 ELECTRIC - FINAL Approved
09/12/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CANNOT USE FLEXIBLE CORD FOR PERMANENT
WIRING METHOD
09/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
COMPLETE ITEM #5 FROM PREVIOUS INSPECTION
09/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEAL OPEN KNOCKOUTS PANEL
2. INSTALL PROTECTIVE BUSHING ON FEEDER CONNECTORS
3. HAVE CUT STRANDS ON GROUND
4. PANEL CANNOT BE RECESSED MORE THAN 1/4"
5. PROVIDE INSTRUCTIONS FOR INSTANT HOT TO VERIFY IT CAN BE CORD & PLUG CONNECTED. PLAN CALLS FOR HARDWIRE WITH LOCK OUT ON BREAKER. SEE NEC 422
6. INSTALL EMT ON ROOF IN NEAT & WORKMANLIKE MANNER USE PROPER BENDS, BLOCKING TO BE SECURED TO ROOF
7. VERIFY SCREWS USE FOR STRAPPING ON ROOF ARE CORROSION PROOF
8. JUNCTION BOX ON ROOF NOT SIZED PROPERLY NEC 314.28
9. UNCHECK DISCONNECT
10. VERIFY NEW FEEDER CONDUCTOR SIZE WITH ENGINEER