Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM #1 NOT CORRECTED BRACING FOR RISER IS CORRECT - THANKS ALSO, NEW WIRING OF RECEPTACLE, NOT GFI PROTECTED OR COMPLETED. ALL HOLES IN BOTTOM OF SERVICE PANEL TO BE PLUGGED ON ADAPTERS INSTALLED CORRECTLY. SUGGEST YOU GET SOMEONE QUALIFIED TO FIX PANEL AND BRING UP TO CODE |
|
| 09/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO GLUE 1/2 FLEX CONDUIT TO ADAPTER GOING INTO SERVICE PANEL 2) NEED TO BOND WATER AND GAS LINE 3) NEED TO USE U.L. LISTED BRACE FOR RISER 4) MIGHT HIRE A ELECTRICIAN TO DO WORK 5) NEXT TIME I WILL REFEE IF CORRECTIONS NOT MET |
|
| 09/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE METER SOCKET TO BLDG 2) SUPPORT RISER PROPERLY 3) BOND WATER ENCLOSURE |
|
| 07/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. RISER SUPPORTS TO BE 1/4" MINIMUM 2. SECURE METER SOCKET TO STRUCTURE 3. BOND METER ENCLOSURE THIS IS RESIDENTIAL |