Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T08CM02542
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2009 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
08/27/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) NEED TO POST BOND FOR RELEASE OF POWER TO TEP |
|
08/13/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BONDING JUMPERS TO BE SIZED PER NEC 250.102 AND 250.66 2) INTSTALL FUSES 3) PROVIDE FAULT CURRENT ANALYSIS AND AIC RATINGS 4) HAVE CREATED PARALLEL NEUTRATL PATH AT SERVICE. REMOVE OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS NEC 250.6 5) NEED TO POST BOND FOR TEMP POWER TO TEST |