Permit: T08CM02542

Parcel: 14111027A


Addresses:

7575 S OLD VAIL RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02542

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/13/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS
08/07/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAP MC CABLE WITHIN 12" OF PANEL
2) REPLACE DAMAGED MC CABLE
3) INSTALL K.O. SEALS WHERE MISSING
4) INSTALL FAR SIDE SUPPORT ON BOXES EXTERIOR WALLS
5) GROUNDS AND NEUTRALS TO BE SEPERATE AT PANEL. CONNECT EQUIPMENT GROUND BAR TO PANEL ENCLOSURE
6) NEED TO PROVID FAULT CURRENT ANALYSIS AND AIC RATING OF EQUIPMENT ON PLANS