Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02542
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/13/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
08/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS |
|
08/07/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STRAP MC CABLE WITHIN 12" OF PANEL 2) REPLACE DAMAGED MC CABLE 3) INSTALL K.O. SEALS WHERE MISSING 4) INSTALL FAR SIDE SUPPORT ON BOXES EXTERIOR WALLS 5) GROUNDS AND NEUTRALS TO BE SEPERATE AT PANEL. CONNECT EQUIPMENT GROUND BAR TO PANEL ENCLOSURE 6) NEED TO PROVID FAULT CURRENT ANALYSIS AND AIC RATING OF EQUIPMENT ON PLANS |