Permit: T08CM02516

Parcel: 122060480


Addresses:

4397 E PIMA ST


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM02516

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
REMOVE FLEX DUCT CONNECTIONS FROM 2ND FLOOR AC UNIT ON ROOF.

RECONNECT WITH SHEETMETAL DUCT.

OK FOR SHEETROCK
08/13/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SHEETROCK EXCEPT SHAFT
FINISH DUCTING INSIDE SHAFT
PROVIDE CONDENSATE TO AN APPROVED LOCATION
PROVIDE ROOF ACCESS