Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM02516

Parcel: 122060480


Addresses:

4397 E PIMA ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
08/19/2008 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
REMOVE FLEX DUCT CONNECTIONS FROM 2ND FLOOR AC UNIT ON ROOF.

RECONNECT WITH SHEETMETAL DUCT.

OK FOR SHEETROCK
08/13/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SHEETROCK EXCEPT SHAFT
FINISH DUCTING INSIDE SHAFT
PROVIDE CONDENSATE TO AN APPROVED LOCATION
PROVIDE ROOF ACCESS