Permit: T08CM02514

Parcel: 11307145A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM02514

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/26/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE FILTRATION ON OUTSIDE AIR (FILTERS ARE IN CEILING)
2. OUTSIDE AIR INLETS ARE TO BE 10' AWAY FROM ALL VENTING OR RAISE VENTS 2' ABOVE
3. PVC PIPING ON ROOF TO BE PAINTED WITH LATEX
4. PVC BLOCKING NOT TO EXCEED 4'
5. EXHAUST FAN VENTS TO HAVE BIRD SCREENS
6. CONTROL WIRING ON ROOF NOT PROPERLY SEALED FOR EXTERIOR APPLICATION (METAL FLEX NOT ALLOWED)
7. PROVIDE PROPER FITTING ON SEAL TITE
8. UNIT DATA PLATES NOT IDENTIFIED
9. ABANDONED ELECTRICAL TO BE COMPLETELY REMOVED
10. PROVIDE BALANCE REPORT
08/22/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*