Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES ON FINAL CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. RUN CONDENSATE DRAINS INSIDE TO THE MOP SINK BLOCK & CLAMP PVC EVERY 4' & PAINT W/LATEX PAINT |
|
| 08/07/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) COMPLETE EXHAUST FANS PER PLANS, IF EXISTING FANS ARE USED, THEY MUST BE CLEANED PRIOR TO INSPECTION. VERIFY 150 CFM. REMOVE EXISTING FLEX FROM ABOVE CEILING THAT IS NOT BEING USED. OK FOR TILES MECHANICAL ONLY |
|
| 08/01/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SEAL ALL DUCT JOINTS WITH 181 APPROVED TAPES OR SEALANT 2. INSTALL STRAPS PER SMACNA STANDARDS |