Permit: T08CM02514

Parcel: 11307145A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02514

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTA-HOT DISCONNECT: ONLY ONE CONDUCTOR PER LUG SEPARATE GROUNDS AND NEUTRALS
LABEL DISCONNECTS

ROOF:
1. CANNOT USE SHEETMETAL THREAD SCREW FOR GROUNDING - 250.8
2. CLEAN SURFACE UNDER LUG - 250.12
08/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CIRCUIT DIRECTORY TO BE AS PER 408.4 LEGIBLE
NO ABBREVIATIONS & CORRECT
2. DISCONNECTING MEANS NEEDED FOR INSTA-HOTS AND PROVIDE INSTALLATION INSTRUCTIONS

ROOF:
1. TIGHTEN LOOSE FITTINGS
2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8
3. BOND JUNCTION BOX ENCLOSURE
08/22/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
08/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*