Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02514
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTA-HOT DISCONNECT: ONLY ONE CONDUCTOR PER LUG SEPARATE GROUNDS AND NEUTRALS LABEL DISCONNECTS ROOF: 1. CANNOT USE SHEETMETAL THREAD SCREW FOR GROUNDING - 250.8 2. CLEAN SURFACE UNDER LUG - 250.12 |
|
08/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CIRCUIT DIRECTORY TO BE AS PER 408.4 LEGIBLE NO ABBREVIATIONS & CORRECT 2. DISCONNECTING MEANS NEEDED FOR INSTA-HOTS AND PROVIDE INSTALLATION INSTRUCTIONS ROOF: 1. TIGHTEN LOOSE FITTINGS 2. RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO - 406.8 3. BOND JUNCTION BOX ENCLOSURE |
|
08/22/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
08/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |