Permit: T08CM02514

Parcel: 11307145A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02514

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/28/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/26/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/22/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
08/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY 8' OF ROD IN CONTACT WITH EARTH
08/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
FINISH #1 & #4 OF PREVIOUS INSPECTION
08/13/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. A BOND FOR TEMP POWER FOR TESTING WILL NEED TO BE POSTED
2. BOXES MORE THAN 1/4" AND/OR 1/8" AROUND OR TO SURFACE - 314.20 & 21
3. PREVENT OBJECTIONABLE CURRENT 250.6
4. GROUNDING ELECTRODE SYSTEM NOT INTACT
5. PROVIDE LISTING FOR "T" FUSE ADAPTORS
6. ENGINEER WILL NOT ACCEPT LIABILITY FOR SERVICE IF WIRED DIFFERENT THAN PLANS
7. PLEASE HAVE ELECTRICIAN OPEN EQUIPMENT
08/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SERVICE INSP: BONDING CONDUCTORS PER 250.66 NEC
AHEAD OF OVERCURRENT #4 CU
2. INSTALL FUSES AND R-PINS
3. PLANS CALL FOR 22K BREAKERS IN PANEL
07/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT M/C CABLE IN SHALLOW STUDS
2. SUPPORT M/C CABLES WITHIN 12" OF BOXES AND TO STRUCTURE

OK WALLS AFTER CORRECTIONS