Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/22/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. YOU MAY NOT USE WEDGE ANCHORS IN MASONRY REPLACE ALL ANCHORS WITH THROUGH BOLTS @ DEMISING WALL TO FINISHED PRODUCT ROOM |
|
| 10/16/2008 | FRAMING | Partial Approval | IVRS - Inspection :* | |
| 10/14/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 27 W. 5TH ST - - REPLACEMENT OF DAMAGED JOISTS 37 W. 5TH ST - - SOUTH ROOF JOISTS MUST HAVE A SET OF APPROVED PLANS @ JOB SITE |
|
| 09/12/2008 | FRAMING | Partial Approval | IVRS - Inspection :* SAME NOTES FOR 27 & 37 W 5TH ST SOUTH SIDE ROOF JOISTS FRAMING ONLY NOTE: 1. NEED APPROVED PLANS ON SITE 2. NEED ROOF NAILING INSPECTION OF ROOF DECKING BEFORE RE-ROOFING STARTS 3. AT ROOF NAILING INSPECTION HAVE LADDER ON SITE |