Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM02481
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. PROVIDE AN AUDIBLE AND VISIBLE ALARM IN A SUPERVISED LOCATION 2. FINISH OVERFLOW SENSORS & DRAIN LINES 3. PROVIDE AIR BALANCE 4. OK FOR CEILING TILES |
|
08/20/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FLEX DUCTS NOT SEALED PER DETAILS ON PLANS. PLANS REQUIRE COPPER CONDENSATE DRAINS. FAN COIL A3-5 HAS NO ACCESS. DO NOT USE PANDUIT STRAPS TO SUPPORT FLEX DUCTS. COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN PLENUM. PROVIDE OVERFLOW SENSORS ON SECONDARY DRAINS. PROVIDE DUCT SMOKE DETECTORS AT EACH FAN COIL ALL TIED TOGETHER W/AUDIBLE AND VISIBLE ALARMS. CONNECT ALL OVERFLOW SENSORS FROM CONDENSATE PUMPS. |