Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM02481

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. PROVIDE AN AUDIBLE AND VISIBLE ALARM IN A SUPERVISED LOCATION
2. FINISH OVERFLOW SENSORS & DRAIN LINES
3. PROVIDE AIR BALANCE
4. OK FOR CEILING TILES
08/20/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
FLEX DUCTS NOT SEALED PER DETAILS ON PLANS.
PLANS REQUIRE COPPER CONDENSATE DRAINS.
FAN COIL A3-5 HAS NO ACCESS.
DO NOT USE PANDUIT STRAPS TO SUPPORT FLEX DUCTS.
COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN PLENUM.
PROVIDE OVERFLOW SENSORS ON SECONDARY DRAINS.
PROVIDE DUCT SMOKE DETECTORS AT EACH FAN COIL ALL TIED TOGETHER W/AUDIBLE AND VISIBLE ALARMS.
CONNECT ALL OVERFLOW SENSORS FROM CONDENSATE PUMPS.