Permit: T08CM02455

Parcel: 125091670


Addresses:

2941 E TOLEDO PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/20/2009 PLUMBING - GAS PRESSURE TEST Approved
08/05/2009 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) TEST FROM 1" STUB UP AT METER TO 1" STUB UP AT WATER HEATER-OK
2) GAS IS ON AT METER INSPECTOR WILL NEED TO SEE MINIMUM SOAP TEST OF FINAL CONNECTIONS AT BOTH ENDS OF PIPING
3) NOTE: SEE BASIC INSTALLATION INSTRUCTIONS PAGE 23 OF RINNAI BOOKLET FOR WATER PIPING AND NOTE #5 PAGE P1.01 FOR INSULATION OF COLD AND HOT WATER PIPING
4) WATER PIPING FOR YARD LINE IS OK
08/04/2009 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) NO ACCESS AT 11:00 AM-GATE LOCKED
07/21/2009 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 10 PSI TEST ON GAS SYSTEM WITH NO LOSS OF PRESSURE FOR 15 MINUTES. TEST GAUGE TO BE IN 1/10 POUND INCREMENTS
2) PROVIDE 1" GAS PIPING PER PLAN
3) PLASTIC GAS PIPING UNDERGROUND REQUIRES MINIMUM 18" OF COVER AND SHALL BE EXPOSED FOR INSPECTION
4) WATER HEATER GAS SHUT OFF VALVE IS REQUIRED TO BE INSTALLED PRIOR TO GAS FLEX WHICH SHALL MEET BTU DEMAND OF WATER HEATER
5) PEX WATER PIPING CANNOT BE EXPOSED TO SUNLIGHT OR IN LOCATIONS WHERE DAMAGE CAN OCCUR
6) INSTALL RINNAI PER MANUFACTURERS INSTALLATION
7) SEAL ALL PIPE PENETRATIONS INTO BLDG