Permit: T08CM02454

Parcel: 134113710


Addresses:

7901 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
11/03/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR TILES MECHANICAL ONLY
10/24/2008 MECHANICAL - ABOVE CEILING Denied 1. WOODEN TRUSSES MUST BE RE-COVERED WITH SHEETROCK
2. COMBUSTIBLE MATERIAL NOT ALLOWED IN A
RETURN PLENUM
3. DO NOT SCHEDULE REINSPECTION FOR MONDAY, THUR, OR FRIDAY NEXT WEEK - MECH. INSPECTOR WILL BE IN TRAINING