Inspection History Details
Permit: T08CM02449
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 08/06/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE SUPPLY & RETURN DIFFUSERS AS PER PLANS SUPPORT ALL FLEX DUCTS EVERY 5' NO DIPS OR SAGS PROVIDE AIR BALANCE REPORT EVERYTHING ON ROOF IS OK |
|
| 07/22/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE ALL CEILING TILES TO EXPOSE DUCT WORK FOR INSPECTION. PROVIDE DUCTING AS PER PLANS. PROVIDE ACCESS TO ROOF. BE SURE CONDENSATE IS TERMINATED TO AN APPROVED LOCATION. ADDRESS OR PERMIT IS NOT CORRECT. HAVE PERMIT CHANGED TO SHOW PROPER ADDRESS. |