Permit: T08CM02449


Addresses:

5470 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED DETAILED PANEL DIRECTORY
2) INSTALL CONDUCTORS ON ROMEX TO TIME CLOCK
3) INSTALL EQUIPMENT GROUNDS ON GROUND BAR IN PANEL
4) HAVE #12 WIRES ON 2 POLE 30 AMP BREAKER
5) CANNOT USE RED WIRE FOR NEUTRAL CONDUCTOR
6) ONE ROOM LOCKED