Inspection History Details
Permit: T08CM02449
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED DETAILED PANEL DIRECTORY 2) INSTALL CONDUCTORS ON ROMEX TO TIME CLOCK 3) INSTALL EQUIPMENT GROUNDS ON GROUND BAR IN PANEL 4) HAVE #12 WIRES ON 2 POLE 30 AMP BREAKER 5) CANNOT USE RED WIRE FOR NEUTRAL CONDUCTOR 6) ONE ROOM LOCKED |