Permit: T08CM02426

Parcel: 12404100A


Addresses:

845 N PARK AV #105

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/05/2009 ELECTRIC - INTERMEDIATE Approved
11/10/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
11/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROTECT PVC STUDS AT BASE PLATE
2. TIGHTEN LOOSE FITTINGS

OK WALLS EXCEPT PANEL WALL AFTER CORRECTIONS
10/30/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NO MORE THAN 360 DEG. IN CONDUIT RUN
OK EXTERIOR WALLS
10/20/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 11 FLOOR BOXES
OK 1" AND 3/4" PVC UNDER SLAB