Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02420
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/13/2008 | ELECTRIC - FINAL | Cancelled | ||
11/13/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
11/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLANS NOT REFLECTIVE OF WORK OR EQUIPMENT INSTALLED PLEASE REVISE |
|
11/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEPARATE GROUND & NEUTRAL AT WATER HEATER DISCONNECT AND HEATER DISCONNECTS 2. NEED HANDLE TIE FOR 2 POLE BREAKERS WATER HEATER & HEATER 3. EXIT/EM LIGHT TO BE ON CIRCUIT FOR AREA SERVED 700.12 4. NO PLANS ON SITE |