Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02420

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/13/2008 ELECTRIC - FINAL Cancelled
11/13/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLANS NOT REFLECTIVE OF WORK OR EQUIPMENT INSTALLED
PLEASE REVISE
11/10/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SEPARATE GROUND & NEUTRAL AT WATER HEATER DISCONNECT AND HEATER DISCONNECTS
2. NEED HANDLE TIE FOR 2 POLE BREAKERS
WATER HEATER & HEATER
3. EXIT/EM LIGHT TO BE ON CIRCUIT FOR AREA SERVED 700.12
4. NO PLANS ON SITE